Saputra, Ande (2026) Analisis Perbandingan Keandalan Penyulang Bandung dan Penyulang Solo Berdasarkan Data Gangguan pada Jaringan Distribusi 20kV PT PLN (Persero) ULP Bengkalis. Other thesis, Politeknik Negeri Bengkalis.
TA-3204221542-Abstract.pdf - Submitted Version
Available under License Creative Commons Attribution Non-commercial Share Alike.
Download (269kB)
TA-3204221542-Bab I Pendahuluan.pdf - Submitted Version
Available under License Creative Commons Attribution Non-commercial Share Alike.
Download (292kB)
TA-3204221542-Daftar Pustaka.pdf - Submitted Version
Available under License Creative Commons Attribution Non-commercial Share Alike.
Download (273kB)
TA-3204221542-Full Text.pdf - Submitted Version
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.
Download (1MB) | Request a copy
Abstract
The reliability of the electric power distribution system is the main indicator in ensuring the continuity of electricity services to customers. External interference, particularly wildlife activities such as monkeys, often triggers outages that impact system performance. This study aims to analyze and compare the reliability level of Bandung feeders and Solo feeders at PT PLN (Persero) ULP Bengkalis based on data on disturbances due to monkey activity in the January-June 2025 and January-June 2026 periods. The research method was carried out quantitatively comparatively by calculating the System Average Interruption Frequency Index (SAIFI) and System Average Interruption Duration Index (SAIDI) based on IEEE Std 1366 guidelines, then comparing it with the SPLN 68-2:1986 standard. The results of the analysis show that Bandung feeders will experience an increase in reliability in 2026 with a decrease in SAIFI from 3.316 to 0.308 times/customer, and SAIDI from 0.337 to 0.060 hours/customer. On the other hand, Solo feeders experienced a worsening of the duration of blackouts (SAIDI) from 0.073 hours/customer in 2025 to 0.219 hours/customer in 2026 due to obstacles in tracing animal disturbances. The two feeders in general still meet the SPLN 68-2:1986 standard in the 2026 period. This study recommends technical interventions such as the installation of silicone rubber insulation covers, animal guards, and the formulation of Right of Way (ROW) vegetation to suppress animal disturbances.
| Item Type: | Thesis (Other) |
|---|---|
| Uncontrolled Keywords: | reliability of distribution system, SAIDI, SAIFI, feeder, monkey disturbance. |
| Subjects: | 600 – ILMU TEKNIK DAN ILMU TERAPAN > 625 – Teknik Kelistrikan dan Elektronik > 625.2 – Sistem Tenaga Listrik dan Distribusi |
| Divisions: | Jurusan Teknik Elektro > Sarjana Terapan (D-IV) Teknik Listrik > SKRIPSI |
| Depositing User: | TEKNIK LISTRIK 2022 Kelas C |
| Date Deposited: | 26 Aug 2026 08:37 |
| Last Modified: | 26 Aug 2026 08:37 |
| URI: | https://eprints.polbeng.ac.id/id/eprint/6826 |