Sitompul, Tinesia (2025) Analisa Sistem Distribusi 20 Kv Penyulang Bandung Jurusan Sei Alam Menggunakan Metode Saidi Pada PT PLN (Persero) ULP Bengkalis. Other thesis, Politeknik Negeri Bengkalis.
![[thumbnail of Abstract]](https://eprints.polbeng.ac.id/style/images/fileicons/text.png)
1. TA_3204211460_Abstract.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.
Download (269kB)
![[thumbnail of Bab I Pendahuluan]](https://eprints.polbeng.ac.id/style/images/fileicons/text.png)
2. TA_3204211460_Bab I Pendahuluan.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.
Download (430kB)
![[thumbnail of Daftar Pustaka]](https://eprints.polbeng.ac.id/style/images/fileicons/text.png)
3. TA_3204211460_Daftar Pustaka.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.
Download (227kB)
![[thumbnail of Full Text]](https://eprints.polbeng.ac.id/style/images/fileicons/text.png)
4. TA_3204211460_Full Text.pdf - Submitted Version
Restricted to Registered users only
Available under License Creative Commons Attribution Share Alike.
Download (4MB) | Request a copy
Abstract
This study aims to analyze the reliability of the 20 kV electrical distribution system on the Bandung Feeder, Sei Alam Section at PT PLN (Persero) ULP Bengkalis using the SAIDI (System Average Interruption Duration Index) method.
The analysis is based on outage data recorded from January to May 2025, covering the types of outage, outage durations, number of affected customers, and the causes of the outage. The SAIDI method is employed to calculate the average duration of interruptions experienced by each customer during the observation period.The analysis results indicate that the monthly SAIDI values range from 6.11 to 20.10 minutes/customer/month,with a five-month total of 51.66
minutes/customer/semester. This value remains significantly below the standard threshold set by SPLN 68-2:1986, which is 21 hours/customer/year. The main causes of distribution network disturbances were identified as external factors, such as trees and animals, as well as internal factors like loose connections. Based on these findings, it can be concluded that the distribution system in the Sei alam section of Bandung Feeder, demonstrated a reliable performance during the observation period.
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | Distribution system reliability, SAIDI, Network disturbance, Bandung Feeder, SPLN 68-2:1986 |
Subjects: | 600 – ILMU TEKNIK DAN ILMU TERAPAN > 625 – Teknik Kelistrikan dan Elektronik > 625.2 – Sistem Tenaga Listrik dan Distribusi |
Divisions: | Jurusan Teknik Elektro > Sarjana Terapan (D-IV) Teknik Listrik > SKRIPSI |
Depositing User: | D-IV Teknik Listrik Kelas C |
Date Deposited: | 21 Aug 2025 08:24 |
Last Modified: | 21 Aug 2025 08:24 |