Analisa Indeks Keandalan Sistem dan ENS (Energy Not Supplied) pada Jaringan Saluran Udara Tegangan Menengah di Penyulang Bandung RC Pematang Duku PT PLN (Persero) ULP Bengkalis

Muslimah, Bella (2025) Analisa Indeks Keandalan Sistem dan ENS (Energy Not Supplied) pada Jaringan Saluran Udara Tegangan Menengah di Penyulang Bandung RC Pematang Duku PT PLN (Persero) ULP Bengkalis. Other thesis, Politeknik Negeri Bengkalis.

[thumbnail of Abstract] Text (Abstract)
TA-3204211446-Abstract.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (149kB)
[thumbnail of Bab I Pendahulu] Text (Bab I Pendahulu)
TA-3204211446-Bab I Pendahuluan.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (211kB)
[thumbnail of Daftar Pustaka] Text (Daftar Pustaka)
TA-3204211446-Daftar Pustaka.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (136kB)
[thumbnail of Full Text] Text (Full Text)
TA-3204211446-FullText.432.pdf - Submitted Version
Restricted to Registered users only
Available under License Creative Commons Attribution Share Alike.

Download (1MB)

Abstract

This practical work research was conducted at PT PLN (Persero) ULP Bengkalis with the aim of analyzing the reliability level of the electricity distribution network system at the Bandung RC Pematang Duku Feeder. The analysis was carried out using three main indicators, namely the System Average Interruption Duration Index (SAIDI), the System Average Interruption Frequency Index (SAIFI), and Energy Not Supplied (ENS), based on power outage data for the period January–June 2025. The results of the analysis showed that the SAIDI value was in the range of 4.79–10.08 hours/month, exceeding the standard limits set by ULP Bengkalis and SPLN 68-2:1986 in most months, so that the duration of the blackout was declared unreliable. On the other hand, the SAIFI value of 0.40–0.71 times/month fully met both standards, indicating that the main problem lies in the length of system recovery, not the frequency of interruptions. Based on the ENS calculation and the estimated economic loss, the total loss was Rp 9,369,283.2 during the observation period. These results are expected to serve as a reference in efforts to improve the reliability of distribution networks in the relevant work areas.

Item Type: Thesis (Other)
Uncontrolled Keywords: SAID, SAIFI, ENS, SUTM, Network Reliability, Economic Loss, Bandung RC Pematang Duku Feeder
Subjects: 600 – ILMU TEKNIK DAN ILMU TERAPAN > 625 – Teknik Kelistrikan dan Elektronik > 625.2 – Sistem Tenaga Listrik dan Distribusi
Divisions: Jurusan Teknik Elektro > Sarjana Terapan (D-IV) Teknik Listrik > SKRIPSI
Depositing User: D-IV Teknik Listrik Kelas C
Date Deposited: 17 Sep 2025 07:52
Last Modified: 18 Sep 2025 07:21
URI: https://eprints.polbeng.ac.id/id/eprint/2979

Actions (login required)

View Item
View Item