Pt.Indah Kiat Pulp & Paper Perawang Tbk Kalibrasi Control Valve Untuk Spray Water Di Multifuel Boiler 26

Ananda, Tri Bryan (2025) Pt.Indah Kiat Pulp & Paper Perawang Tbk Kalibrasi Control Valve Untuk Spray Water Di Multifuel Boiler 26. Other thesis, Politeknik Negeri Bengkalis.

[thumbnail of Abstrak] Text (Abstrak)
1.TA-3103221322-Abstrak.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (1MB)
[thumbnail of Bab I Pendahuluan] Text (Bab I Pendahuluan)
2.TA-3103221322-Bab I Pendahuluan.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (1MB)
[thumbnail of Daftar Pustaka] Text (Daftar Pustaka)
3.TA-3103221322-Daftar Pustaka.pdf - Submitted Version
Available under License Creative Commons Attribution Share Alike.

Download (1MB)
[thumbnail of Full Text] Text (Full Text)
4.TA-3103221322-Full Text.pdf - Submitted Version
Restricted to Registered users only
Available under License Creative Commons Attribution Non-commercial Share Alike.

Download (2MB) | Request a copy

Abstract

This research discusses the calibration process ofthecontrol valve for spray water in Multifuel Boiler 26 at PT. Indah Kiat Pulp & Paper Perawang. The control valve is a crucial component in industrial controlsystems,functioningtoregulate fluid flow based on input signals from the control system. Observations showed that before calibration, the valve opening position did not meet the standard; for example, at 4 mA input, the valve opened 10% instead of 0%, and at 20 mA input, it only reached 95% instead of the required 100%. After calibration by adjusting the zero and span using a
hart communicator, the results met the standard, with the valve opening linearly proportional to the 4–20 mA input signal. The findings indicate that calibration improves the accuracy of the control valve’s performance, making the spray water control system more stable and efficient. Proper documentation of calibration results is also essential as a reference for routine maintenance to ensure optimal system performance and reduce the risk of failure.

Item Type: Thesis (Other)
Uncontrolled Keywords: Calibration, Control Valve, Spray Water, Multifuel Boiler, PT. Indah Kiat Pulp & Paper
Subjects: 600 – ILMU TEKNIK DAN ILMU TERAPAN > 625 – Teknik Kelistrikan dan Elektronik > 625.3 – Elektronika Daya dan Kontrol
Divisions: Jurusan Teknik Elektro > Diploma Tiga (D-III) Teknik Elektronika > TUGAS AKHIR
Depositing User: D-III Teknik Elektronika Tahun 2022
Date Deposited: 19 Sep 2025 01:12
Last Modified: 19 Sep 2025 07:17
URI: https://eprints.polbeng.ac.id/id/eprint/2994

Actions (login required)

View Item
View Item